Connecting HID interface modules for Synergis™ Cloud Link - Synergis™ Cloud Link

Applies to
Synergis™ Cloud Link
Last updated
2022-04-08
Language
English
Product
Synergis™ Cloud Link

Connections for HID interface modules

With the enclosure securely mounted, the peripheral devices, such as readers, the IP network, and AC power source can be connected to the HID interface modules inside the enclosure.

The following diagram is an example of how to connect HID interface modules to readers.

A Reader connections to HID interface modules

HID interface module: Wiring diagram for a Card In/Free Out

You can wire HID interface modules for a "Card In / Free Out door" configuration.

The following diagram demonstrates how to connect HID interface modules (VertX V100 shown) for a “Card In / Free Out”.

IMPORTANT: The system must not be installed in the fail-secure mode unless permitted by the local authority having jurisdiction and must not interfere with the operation of Listed panic hardware.
A Reader connections See Reader connections for HID interface modules (P1 and P4).
B Standard MAG lock See Door monitor and REX input connections for HID interface modules (P2 and P5).
C Door monitor switch N/C See Door monitor and REX input connections for HID interface modules (P2 and P5).
D MAG lock switch See Output connections for HID interface modules (P3 and P6).
E REX switch in Crash Bar See Door monitor and REX input connections for HID interface modules (P2 and P5).
F Door #1 See Door monitor and REX input connections for HID interface modules (P2 and P5).
G Door #2 See Door monitor and REX input connections for HID interface modules (P2 and P5).
H Electric Door Strike (Lock) See Output connections for HID interface modules (P3 and P6).
I PIR or REX See Door monitor and REX input connections for HID interface modules (P2 and P5).
J 12 or 24 VDC power supply  
K Horn or Strobe  
L Termination jumper If the interface module will be attached to the end of the RS-485 bus, install a terminating jumper to the "In" position on the termination resistor pins.
M Address dial Use thumbnail to turn dial and set address.

Reader connections for HID interface modules (P1 and P4)

As part of the connecting the HID interface modules, you must connect the door reader wires to pins at locations P1 and P4.

For a visual representation of the HID interface module connections, see Connections for HID interface modules.
NOTE: You cannot unplug a connector from one side and plug it into the corresponding connector on the other side. Connectors on VertX devices are positioned to be mirror images and are not interchangeable.

The following connection information is for readers that come with a pig-tail cable. Note that the wire colors that are shown might not apply to readers with screw terminals.

P1 signal Wire color Pin   Pin Wire color P4 signal
Reader power red 1   10 red Reader power
Ground black 2   9 black Ground
Data 0 / Data green 3   8 green Data 0 / Data
Data 1 / Clock white 4   7 white Data 1 / Clock
Data Return not used 5   6 not used Data Return
Green LED orange 6   5 orange Green LED
Red LED brown 7   4 brown Red LED
Beeper yellow 8   3 yellow Beeper
Hold/Card Pres blue 9   2 blue Hold/Card Pres
Shield   10   1   Shield

Output connections for HID interface modules (P3 and P6)

As part of the connecting the HID interface modules, you must set up the HID output connections P3 and P6.

For a visual representation of the HID interface module connections, see Connections for HID interface modules.
IMPORTANT: The system must not be installed in the fail-secure mode unless permitted by the local authority having jurisdiction and must not interfere with the operation of Listed panic hardware.
NOTE: Relays are dry contact rated for 2A/30VDC resistive load, 1.2A/30VDC inductive load.
P3   State Pin   Pin State   P6
Strike Relay (Out 1) Lock Normally open 1   6 Normally open Lock Strike Relay (Out 3)
Common 2   5 Common
Normally closed 3   4 Normally closed
Aux Relay (Out 2)   Normally open 4   3 Normally open   Aux Relay (Out 4)
Common 5   2 Common
Normally closed 6   1 Normally closed

Door monitor and REX input connections for HID interface modules (P2 and P5)

As part of the connecting the HID interface modules, you must connect the door monitor and REX inputs to P2.

For a visual representation of the HID interface module connections, see Connections for HID interface modules.
NOTE:
  • The default REX input configuration is normally open (NO) unsupervised (no EOL resistors).
  • The default door switch (DS) configuration is Normally Closed (NC), unsupervised (no EOL resistors).
  • The Door input monitor was not evaluated by UL.
P2 Label Pin   Pin Label P5
Door monitor +(In 1) 1   4 (In 3)+ Door monitor
-(In 1) 2   3 (In 3)-
REX +(In 2) 3   2 (In 4)+ REX
-(In 2) 4   1 (In 4)-

Remaining inputs for HID interface modules (P7)

As part of the connecting the HID interface modules, you must connect the remaining inputs.

For a visual representation of the HID interface module connections, see Connections for HID interface modules.

Connect remaining inputs. All other input points (except for the 12 VDC) are defaulted for NO switches and are unsupervised. They can be configured for end-of-line resistors of 1 to 6k Ohms. Use the Synergis™ Cloud Link application to configure supervised inputs.

NOTE: Input monitoring was not evaluated by UL.
  Tamper (Input 5) AC Fail (Input 6) Batt Fail (Input 7) 12VDC IN
Label + - + - + - - +
Pin# 8 7 6 5 4 3 2 1

HID V200 connections

As part of a Synergis™ installation, you may need to include a HID V200 Input Monitor Interface.

The following diagram shows the connections for a V200 Input Monitor Interface.

A Inputs Tamper and power monitor.
B Power In Connect + to red (observe polarity). Connect - to black. Use 20 AWG wires minimum.
C Inputs 16 general-purpose, programmable-circuit type.
D Address switches Rotary address switch (0–15).
E Relay outputs 2A @ 30 VDC, inductive 0.6 PF
F Line termination Install a terminating jumper on the “In” position of the interface module at the end of the RS-485 bus.
G RS-485 RS-485 bus connection to other modules.

HID V300 connections

As part of a Synergis™ installation, you might need to include a HID V300 Output Control Interface.

The following diagram shows the connections for a V300 Output Control Interface.

A Inputs Tamper and power monitor.
B Power In Connect + to red (observe polarity). Connect - to black. Use 20 AWG wires minimum.
C Relays 12 latching Form-C relays, contacts rated at 2A at 30 VDC
D Address switches Rotary address switch (0–15).
E Inputs 2A @ 30 VDC, inductive 0.6 PF
F Line termination Install a terminating jumper on the “In” position of the interface module at the end of the RS-485 bus.
G RS-485 RS-485 bus connection to other modules.