Connections for HID interface modules
With the enclosure securely mounted, the peripheral devices, such as readers, the IP network, and AC power source can be connected to the HID interface modules inside the enclosure.
The following diagram is an example of how to connect HID interface modules to readers.
A | Reader connections to HID interface modules |
HID interface module: Wiring diagram for a Card In/Free Out
You can wire HID interface modules for a "Card In / Free Out door" configuration.
The following diagram demonstrates how to connect HID interface modules (VertX V100 shown) for a “Card In / Free Out”.
Reader connections for HID interface modules (P1 and P4)
As part of the connecting the HID interface modules, you must connect the door reader wires to pins at locations P1 and P4.
The following connection information is for readers that come with a pig-tail cable. Note that the wire colors that are shown might not apply to readers with screw terminals.
P1 signal | Wire color | Pin | Pin | Wire color | P4 signal | |
---|---|---|---|---|---|---|
Reader power | red | 1 | 10 | red | Reader power | |
Ground | black | 2 | 9 | black | Ground | |
Data 0 / Data | green | 3 | 8 | green | Data 0 / Data | |
Data 1 / Clock | white | 4 | 7 | white | Data 1 / Clock | |
Data Return | not used | 5 | 6 | not used | Data Return | |
Green LED | orange | 6 | 5 | orange | Green LED | |
Red LED | brown | 7 | 4 | brown | Red LED | |
Beeper | yellow | 8 | 3 | yellow | Beeper | |
Hold/Card Pres | blue | 9 | 2 | blue | Hold/Card Pres | |
Shield | 10 | 1 | Shield |
Output connections for HID interface modules (P3 and P6)
As part of the connecting the HID interface modules, you must set up the HID output connections P3 and P6.
P3 | State | Pin | Pin | State | P6 | |||
---|---|---|---|---|---|---|---|---|
Strike Relay (Out 1) | Lock | Normally open | 1 | 6 | Normally open | Lock | Strike Relay (Out 3) | |
Common | 2 | 5 | Common | |||||
Normally closed | 3 | 4 | Normally closed | |||||
Aux Relay (Out 2) | Normally open | 4 | 3 | Normally open | Aux Relay (Out 4) | |||
Common | 5 | 2 | Common | |||||
Normally closed | 6 | 1 | Normally closed |
Door monitor and REX input connections for HID interface modules (P2 and P5)
As part of the connecting the HID interface modules, you must connect the door monitor and REX inputs to P2.
- The default REX input configuration is normally open (NO) unsupervised (no EOL resistors).
- The default door switch (DS) configuration is Normally Closed (NC), unsupervised (no EOL resistors).
- The Door input monitor was not evaluated by UL.
P2 | Label | Pin | Pin | Label | P5 | |
---|---|---|---|---|---|---|
Door monitor | +(In 1) | 1 | 4 | (In 3)+ | Door monitor | |
-(In 1) | 2 | 3 | (In 3)- | |||
REX | +(In 2) | 3 | 2 | (In 4)+ | REX | |
-(In 2) | 4 | 1 | (In 4)- |
Remaining inputs for HID interface modules (P7)
As part of the connecting the HID interface modules, you must connect the remaining inputs.
Connect remaining inputs. All other input points (except for the 12 VDC) are defaulted for NO switches and are unsupervised. They can be configured for end-of-line resistors of 1 to 6k Ohms. Use the Synergis™ Cloud Link application to configure supervised inputs.
Tamper (Input 5) | AC Fail (Input 6) | Batt Fail (Input 7) | 12VDC IN | |||||
---|---|---|---|---|---|---|---|---|
Label | + | - | + | - | + | - | - | + |
Pin# | 8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 |
HID V200 connections
As part of a Synergis™ installation, you may need to include a HID V200 Input Monitor Interface.
The following diagram shows the connections for a V200 Input Monitor Interface.
A | Inputs | Tamper and power monitor. |
B | Power In | Connect + to red (observe polarity). Connect - to black. Use 20 AWG wires minimum. |
C | Inputs | 16 general-purpose, programmable-circuit type. |
D | Address switches | Rotary address switch (0–15). |
E | Relay outputs | 2A @ 30 VDC, inductive 0.6 PF |
F | Line termination | Install a terminating jumper on the “In” position of the interface module at the end of the RS-485 bus. |
G | RS-485 | RS-485 bus connection to other modules. |
HID V300 connections
As part of a Synergis™ installation, you might need to include a HID V300 Output Control Interface.
The following diagram shows the connections for a V300 Output Control Interface.
A | Inputs | Tamper and power monitor. |
B | Power In | Connect + to red (observe polarity). Connect - to black. Use 20 AWG wires minimum. |
C | Relays | 12 latching Form-C relays, contacts rated at 2A at 30 VDC |
D | Address switches | Rotary address switch (0–15). |
E | Inputs | 2A @ 30 VDC, inductive 0.6 PF |
F | Line termination | Install a terminating jumper on the “In” position of the interface module at the end of the RS-485 bus. |
G | RS-485 | RS-485 bus connection to other modules. |