The Telenot Intrusion Panel driver 5.0.0 includes the following known limitations.
Issue | Description |
---|---|
3055607 | When a Telenot panel is in the tamper state, the related buzzer cannot be deactivated. |
3055608 | You cannot change the state of a Telenot panel from perimeter armed to master armed. |
3055609 | The firmware version used by Telenot panels cannot be viewed in Security Center. |
3055610 | The MAC address of Telenot panels cannot be viewed in Security Center, as panels don't have Ethernet connectors. |
3055611 | The tamper state of a panel is not indicated when the panel comes online. This state is only indicated when a tamper event is received from the panel. |
3055613 | The state of an input alarm can only be retrieved when an event is sent from the panel. |
3055614 | Bypassing and unbypassing inputs on Telenot panels is not supported. |
3055615 | Pushing or pulling users to and from Telenot panels is not supported. |
3055616 | Delayed arming mode of an intrusion area is not supported by Telenot panels. |
3055617 | Forced arming of an intrusion area is not supported by Telenot panels. |
3057165 | At a minimum, Telenot panels are unable to support more than one command per three seconds. This delay can increase if multiple extensions are installed. |
3057172 | Triggering alarms on an intrusion area is not supported by Telenot panels. |
3057173 | Bypassing the arming of an intrusion area is not supported by Telenot panels. |
3057174 | The Genetec™ Intrusion Protocol extension can set the time on a panel, but reading the time on a panel is not supported. |
3058283 | The names of intrusion areas, inputs, and outputs on Telenot panels are not
automatically imported by the extension. Workaround: In Genetec™ Intrusion Protocol extension, click the Import button
on the configuration page of the unit.
|