To monitor the data points of a device or entity, you must add
them
to the device in Security Center.
Procedure
-
From the Config
Tool home page,
open the Plugins task.
-
Select a Modbus device or entity from the entity browser and click the
Properties tab.
-
In the Data points section, click Add data
point (
) and enter the following:
- Name
- The name of the data point.
- Modbus
Object
Type
- The object type of the data point. This can be a coil, discrete
input, holding register, or input register.
- Address
- The address of the data point on the device. You can enter the
address in decimal format and then click Hex
to convert it to hexadecimal.
- Type
- The type of information reported by the input (data point). The
types of data and the possible values that can be reported are:
- Boolean
- True or False
- Int16
- -32,768 to 32,767
- UInt16
- 0 to 65,535
- Byte
- 0 to 255
- Unit
- The unit of measure of the data point.
This
field is optional.
- Unit symbol
- A symbol to represent the unit of measure of the data point. This
field is optional.
-
Click Add and then click
Apply.
Results
The data point is displayed in the
Data
points section.