To monitor the data points of a OPC UA Server device or entity, you must add them to the device or entity in Security Center.

Before you begin

Best Practice: For optimal performance of the plugin, it is recommended to limit the number of data points and rules to 5000 respectively.

Procedure

To add a data point to an OPC Client device or entity:

  1. From the Config Tool homepage, open the Plugins task.
  2. In the entity browser, select the Industrial IoT role and click on the Devicestab.
  3. Select the OPC Client device from the Devices list.
  4. In the Data points section of the device, click Add a data point ().
    The Add a data point dialog box opens.
  5. Beside the Node ID field, click Open OPC server browser ().
    The Select OPC node dialog box opens.
    Dialog box for selecting a single OPC data point to add.
  6. Select a data point from the browser and click Select.
    In the Add a data point dialog box, the protocol information is filled.
  7. Enter the rest of the information.
    Dialog bo.x for adding a single OPC data point.
    Value type
    The type of information reported by the input (data point).
    Access level
    Indicates whether the selected data point is read-only or read-write. This field is automatically displayed by the plugin role.
    Conversion
    The conversion to be applied to the argument.
    Unit name
    (Optional) The measurement unit of the data point.
    Unit symbol
    (Optional) The symbol representing the measurement unit.
  8. Click Add to add another data point or click Add and Close.
    The data point is displayed in the Data points section.

To add multiple data point at the same time:

  1. In the Data points section, instead of clicking Add a data point (), click () instead.
    The Add data points dialog box opens.
  2. Expand the nodes and select the data points you want to add, and click Add.
    Dialog box for adding multiple OPC data points at the same time..
    All selected data points are added at the same time.
  3. (Optional) Select the data points one by one and configure the Unit name and Unit symbol.
  4. (Optional) To duplicate a data point, right-click on the data point and select Duplicate.
  5. (Optional) To deactivate a data point, right-click on the data point and select Deactivate.
  6. Click Apply.