The Industrial IoT plugin 5.2.3.0 includes the following known limitations.
Issue | First reported in | Description |
---|---|---|
2283648 | OPC Client 4.2, Modbus 4.2, BACnet 4.2, SNMP Manager 4.2 | Custom events from federated systems are displayed incorrectly in reports
generated by the local Security Center
system. Workaround: Make sure the custom events from the federated system
are using the same ID as custom events in the local system.
|
1867639 | OPC Client 3.1 | When the OPC Client plugin is connected to an OPC UA server behind a DA Gateway, the OPC UA server is displayed as Connected in the plugin, even if the OPC UA server is offline. |
1763634 | Modbus 3.0 GA | The Modbus plugin only works when RabbitMQ is installed by Genetec Inc. software. Workaround: If the
computer hosts a version of RabbitMQ installed by a third-party application, either
uninstall RabbitMQ and then install the Modbus plugin, or install the Modbus plugin
on a different machine.
|