The Genetecâ„¢ Receiver extension 3.2.0 includes the following known issues.
Issue | Description |
---|---|
2491784 | When an event code mapping is modified and given the same event code as a different mapping, the triggered error message references creating an event code instead of modifying one. |
2437567 | Bosch Receiver: AC fail, Battery fail, and Tampered events put the unit in a warning state, but are not checked off in the System status task. |
1632896 | When panels are added to a deactivated receiver, the panels get added to the license count. Hence, fewer licenses are available for active receiver units. Deactivated receivers should not consume licenses. |
1631169 | When a deactivated receiver has more panels than available licenses, it is
possible to activate the receiver and add more panels. When the receiver is
deactivated, it no longer releases licenses. Deactivating a receiver should release
all panel licenses. Workaround: To release the panel licenses, deactivate
the receiver, and then in Server Admin, restart the Security Center
Directory.
|
1624197 | When an intrusion detection unit is offline because a license is unavailable,
it does not come back online automatically when a license is released. Workaround: Make sure you have a license available. Deactivate the offline
unit, and then activate it.
|
1622958 | Some receivers send the same event message when an event first occurs (opens)
and when it ends (closes). Workaround: Look at the description to see if
the event was opened or closed.
|
1617632 | When adding multiple alarm receivers, each receiver must be assigned a unique port number, even if the receivers have different IP addresses. |
1601488 | If a user has a panel or area selected in the Unit
mappings page of an intrusion detection unit, and the system
automatically creates a new area or input for that unit, then the page is not
updated to show the new entity. Workaround: Refresh the Unit
mappings page to see new entities.
|