You can use the three inputs on the Synergis™ Cloud
Link
appliance to monitor the physical installation of the appliance. For example, you can connect
an input to a tamper switch on the enclosure in which the appliance is installed.
What you should know
- You can set a special behavior for each input. Each special behavior corresponds to
an event that you can receive in the Monitoring task:
Special behavior |
Security Center
event |
AC failure |
AC fail |
Tamper switch |
Hardware tamper |
Battery failure |
Battery fail |
- Only Input 1 can be supervised. The Input configuration
options are present for the other inputs, but changing them does not do
anything.
- You can view the state changes of the inputs on the I/O
diagnostics page in the Synergis™ Appliance Portal.
Procedure
-
From the Config
Tool home page, open
the Access control task, and click the Roles and
units view.
-
Select your Synergis™ Cloud
Link unit, and click the
Hardware tab.
-
Click the Onboard IO tab, and then configure the
inputs:
- Special behavior
- The special behaviors determine the event that you receive in the
Monitoring task when the input is in non-normal
state. By default, the special behavior is set to
None. Select one of the following:
- AC failure
- Tamper switch
- Battery failure
- Input configuration
- For Input 1 only, select one of the following:
- Unsupervised
- Input 1 is unsupervised by default.
- Three states
- Select one of the pre-configured options, which selects the
Resistance range for you, or select
Custom, and enter the Lower
Limit (Ohms) and Higher Limit
(Ohms) in ohms yourself.
- Four states
- Select one of the pre-configured options, which selects the
Closed range and Open
range for you, or select
Custom, and enter the Lower
Limit (Ohms) and Higher Limit
(Ohms) values yourself.
-
Click Apply.
-
Click the Peripherals tab, and double-click the input you
configured on the Hardware page.
-
(Optional) In the Edit Input dialog box, enter a new name and
logical ID.
-
Set the Contact type:
-
For Input 1 only, select Not supervised, 3
state supervised, or 4 state supervised
to match the value you selected for the Input
configuration on the Hardware page.
-
Select Normally open or Normally
closed.
-
Click Save.
Results
When an input is in a non-normal state, the
Synergis™ Cloud
Link unit turns yellow, and you receive an entity warning. If you were monitoring the
Synergis™ Cloud
Link unit and the special behavior events, you
receive the event corresponding to the input's special behavior in the