Starting in Synergis™ Softwire 11.3.1 and Security Center 5.10.4.0, Mercury LP1502, LP4502, MR50-S3, and
MR52-S3 controllers support two OSDP readers per port through a setting configured in the
Synergis™ Appliance Portal.
What you should know
If the
Two OSDP readers per reader port option is enabled, and
you only configure one of the OSDP readers on a door, ensure that the reader you use is the
primary reader, otherwise, the door will be in warning, even though it still works.
Procedure
-
In the Synergis™ Appliance Portal, enable the Two OSDP
readers per reader port option on the Mercury controller
settings page.
NOTE: When this option is enabled, the Smart card option configured
on the OSDP reader in Config Tool is on by
default, and remains on in the background, even if you turn off the option.
-
Restart Synergis Softwire.
-
Add two OSDP readers to the reader port of the Mercury controller:
-
From the Config Tool homepage, open
the Access control task, and click the Roles and
units view.
-
From the entity tree, select the Synergis™
unit, and click the Peripherals tab.
-
Double-click Reader 1, and configure the following
settings:
- Type of reader
- Select OSDP 2.
- Baud rate
- Select a bit rate.
- Address
- Select the address you configured for the first reader.
-
Click Save.
-
Double-click Reader 1 Out, and select the address you
configured for the second reader.
NOTE: Only the address needs to be configured because Reader 1 and Reader 1
Out use the same configuration, except the address.
-
Assign the readers to a door.
Example:
Reader 1 and Reader 1 Out must be set on the same
door, and Reader 2 and Reader 2 Out must be set on the same door.
-
If the controller has a second reader port, you can repeat step 3 to configure
Reader 2 and Reader 2 Out on the second port.
After you finish
Pair the OSDP readers in the Synergis™ Appliance Portal. When using OSDP 2, you might need
to disable
Install mode on the reader after pairing if it is not disabled after
pairing.