OSDP readers must
have their RS-485 bit rate and address configured before they can be used. You can configure
your readers directly from the Synergis™ Appliance Portal by creating an OSDP channel with
Programming mode enabled.
What you should know
- For OSDP readers you want connected to a Mercury unit, using this procedure, followed by
setting the reader's physical
address in the Synergis Appliance Portal replaces using a configuration card to
set the reader's baud rate and physical address.
- When Programming mode is enabled, you can only have one online reader connected to the
RS-485 channel at a time.
Procedure
-
Log on to the
Synergis
unit.
-
Click .
-
At the top of the Hardware column, click
Add ().
-
In the Add hardware dialog box, select OSDP
as the Hardware type.
-
Select the Channel
(A, B, C, or
D)
.
NOTE:
If your Synergis unit has an optional
expansion module, then you have additional channels. For more
information, see the SY-CLOUDLINK-312 Quick Start
Guide.
-
Under Interface module type, click
Add.
-
Click Save.
The channel and interface are created.
-
From the hardware tree, select the OSDP channel you created and click
Edit ().
-
From the Bits per second list, select the bit rate you want to
configure for your device.
-
If you are adding a reader, select the Programming mode check
box.
If you have a configuration card, you can use it instead of
Programming
mode. See the documentation that came with your
card.
-
Click Save.