OSDP devices, such as secure I/O modules and readers, must have their RS-485 bit rate
and address configured before they can be used. To configure your readers in the Synergis™
Appliance Portal, you must create an OSDP channel with Programming mode enabled.
What you should know
- For OSDP readers that you want connected to a Mercury unit: Instead of using a
configuration card to set the reader's baud rate and physical address, you can follow this
procedure, and then set the reader's physical
address in the Synergis Appliance Portal.
- When Programming mode is enabled, you can only have one online reader connected to the
RS-485 channel at a time.
Procedure
-
Log on to the
Synergis
unit.
-
Click .
-
At the top of the Hardware column, click
Add (
).
-
In the Add hardware dialog box, select OSDP
as the Hardware type.
-
Select the Channel
(A, B, C, or
D)
.
NOTE:
If your Synergis unit has an optional
expansion module, then you have additional channels. For more
information, see the SY-CLOUDLINK-312 Quick Start
Guide.
-
From the Bits per second list, select the bit rate you want to
configure for your device.
NOTE: Select Other from the list to enter a custom bit rate.
-
Under Interface module type, click
Add.
-
Click Save.
The channel and interface are created.
-
From the hardware tree, select the OSDP channel you created and click
Edit (
).
-
If you’re adding a reader, select the Programming mode
checkbox.
If you have a configuration card, you can use it instead of
Programming
mode. See the documentation that came with your
card.
-
Click Save.