Readers connected to the MR62e downstream panel are used in specific pairs and must be configured to predefined addresses, as hard-coded by Mercury, in order to work.

The following table shows the required reader address configuration:
Reader number (address) Door setup Mercury turnstiles and elevators
0 Door 1: Reader side IN Yes
1 Door 2: Reader side IN Yes
2 Door 1: Reader side OUT No
3 Door 2: Reader side OUT No
NOTE: To use the MR62e to control only one card-in/card-out door, use addresses 0 and 2.

To use the MR62e to control two card-in/REX-out doors, use addresses 0 and 1.