Before you can enroll a DDS IP controller on the Synergis™ unit, you must assign a static IP address to its
TCP/IP extension board by connecting to it through a serial port.
Before you begin
Ensure that you have the following:
- Setup program for Tibbo Device Server Toolkit (either tdst-5-09-12-x64.exe
or tdst-5-09-12- x86.exe). Ask your Genetec representative.
-
Latest version of Synergis™ Softwire and the Tibbo.sfw plugin.
What you should know
The steps and instructions tagged with Hardening are
optional, but will protect your system against cyberattacks.
Procedure
-
Attach the TCP/IP extension board to the TPL controller.
-
Connect a USB to RS-485 converter cable to your computer.
-
Connect the L and H connectors (circled in red) on the TCP/IP extension board to the
RS-485 connector of your converter cable.
-
Install the Tibbo Device Server Toolkit on your computer.
Choose either the x86 or the x64 package based on the type of machine that you
have.
-
Run Tibbo DS Manager as an administrator (C:\Program
Files\Tibbo\TDST\tdsman.exe) .
-
Click Serial Access and select the COM port corresponding to the
channel to which the TCP/IP extension board is connected.
-
Click Settings, and do one of the following.
- If you see the message Press the setup button on the device, continue with
Step 10.
- If you see the message Unable to open the serial port. The serial port may be in
use by another program, then verify you selected the right COM port, or that no
other program is using the same COM port that is connected to the TCP/IP extension
board.
-
Press the setup button (labeled SW2) on the TCP/IP extension
board.
-
In the Settings dialog box that opens, enter the following:
Network page:
-
DHCP: 0 - Disabled
-
IP-address: IP address assigned to the DDS controller
-
Port: Port number 1001
Connection page:
-
Transport protocol: 1 - TCP
- (Hardening) Link Service Login: 0-Disabled
- (Hardening) Inband commands: 0-Disabled
- (Hardening) Data login: 0-Disabled
- (Hardening) Routing Mode: 0-Server (Slave)
- (Hardening) Accept connection from: 1-Current Destination IP
address
Serial port page:
-
RTS/CTS flow control: 0 - Disabled or remote
-
Baud rate: 3 - 9600 bps
-
Click OK, and then press the setup button on the TCP/IP
extension board when prompted. For the location of the setup button.
-
Disconnect the TCP/IP extension board from your USB to RS-485 converter cable.
-
Connect the TCP/IP extension board to the same subnet where the Synergis unit is found.
The Ethernet connector is located under the label Tibbo on the
TCP/IP extension board.