Before you enroll the Mercury controller on the Synergis™ unit, you must assign a static IP address to the
controller.
Before you begin
Make sure you have the following:
- Mercury Setup and Configuration Guide
- Instruction manual for connecting to the web portal of your Mercury controller and
setting up its IP address (and other configurations).
- Static IP address
- Static IP address assigned to the controller by your IT department.
- Physical addresses
- Each interface panel attached to the same RS-485 port of the same Mercury controller
must have a unique physical address (configured on a DIP switch).
Best Practice: If you have many Mercury controllers to enroll on the same Synergis
unit, it is best to enroll them all at the same time. Each controller you add or remove from
the Synergis unit causes the unit to restart. While the unit restarts, it’s offline for
about 30 seconds.
What you should know
Mercury controllers enrolled on the same Synergis unit cannot be assigned different partitions in
Security Center. If you need to assign the
controllers to different partitions, enroll them on different Synergis units, and then assign the Synergis units to different partitions.
NOTE:
The steps and instructions tagged with Hardening are
optional, but will protect your system against cyberattacks.
Procedure
-
On the Mercury controller, set the DIP switch S1-1 to
ON.
This gives you a five-minute window to sign in using factory default settings.
-
Sign in to the Mercury controller through its Configuration
Manager web page. Use the default IP address (
192.168.0.251)
and credentials (admin/password). For more information, see the
manufacturer’s documentation.
-
On the Mercury controller, set the DIP switch S1-1 back to
OFF for normal operation.
This prevents the factory default settings from being used to sign in to the
controller.
-
Select Network from the menu, configure the Mercury controller’s
IP address, and click Accept.
-
Select Host Comm from the menu.
-
In the Host Communication page, configure the following settings,
and click Accept.
- Communication Address
- Set to 0.
IMPORTANT: Not to be confused with the
Channel that must be unique when you enroll the Mercury
controller on the Synergis unit.
- Port Number
- The port number used by the Synergis unit to communicate
with the Mercury controller (default=3001).
- Authorized IP Address Required
- (Hardening) Select this option, and set Authorized IP
address to the IP address of the Synergis
unit.
- Data Security
- Set to TLS Required.
IMPORTANT: If TLS is not
selected, the Mercury controller stays offline.
-
Create a new user on the Mercury controller.
This saves you from having to physically access the unit and set the DIP switch
S1-1 to ON every time you modify the controller
configuration.
-
From the left-side menu, click Users.
-
Under the users list, click New User.
The
User Account page opens.
-
Enter a new Username and a strong
Password.
-
Confirm the password, and then click Save.
The Users page opens and the new user is added to the
list.
-
Under Time Server, select Disable.
The Time Server is not required. Synergis™ Softwire monitors and automatically sets
the time on the Mercury units.
-
(Hardening) Next to SNMP Options, select
Disabled, and then click Submit.
-
From the left-side menu, click Apply Settings, and then click
Apply Settings, Reboot.