Mercury reader address configuration for MR62e panel - Synergis Cloud Link 2.0.4

Synergis™ Cloud Link Administrator Guide 2.0.4

Applies to
Synergis Cloud Link 2.0.4
Last updated
2023-01-31
Content type
Guides > Administrator guides
Language
English
Product
Synergis Cloud Link
Version
2.0

Readers connected to the MR62e downstream panel must be addressed and used in specific pairs to work.

The following table shows the required reader address configuration:
Reader number (address) Door setup Mercury turnstiles and elevators
0 Door 1: Reader side IN Yes
1 Door 2: Reader side IN Yes
2 Door 1: Reader side OUT No
3 Door 2: Reader side OUT No
NOTE: To use the MR62e to control only one Card In/Card Out door, use addresses 0 and 2.

To use the MR62e to control two Card In/REX Out doors, use addresses 0 and 1.