Creating a channel to configure OSDP readers in the Synergis™ Appliance Portal - Synergis Cloud Link 2.1.1

Synergis™ Cloud Link Administrator Guide 2.1.1

Applies to
Synergis Cloud Link 2.1.1
Last updated
2023-04-12
Content type
Guides > Administrator guides
Language
English
Product
Synergis Cloud Link
Version
2.1

OSDP readers must have their RS-485 bit rate and address configured before they can be used. You can configure your readers directly from the Synergis™ Appliance Portal by creating an OSDP channel with Programming mode enabled.

What you should know

  • For OSDP readers you want connected to a Mercury unit, using this procedure, followed by setting the reader's physical address in the Synergis™ Appliance Portal replaces using a configuration card to set the reader's baud rate and physical address.
  • When Programming mode is enabled, you can only have one online reader connected to the RS-485 channel at a time.

Procedure

  1. Log on to the Synergis Cloud Link unit.
  2. Click Configuration > Hardware.
  3. At the top of the Hardware column, click Add ().
  4. In the Add hardware dialog box, select OSDP as the Hardware type.
  5. Select the Channel (1 - 4).
    NOTE: If you have the Synergis Cloud Link 312 unit, then you have up to 12 channels. For more information, see About the Synergis Cloud Link 312 RS-485 ports.
  6. Under Interface module type, click Add.
    Add hardware dialog box showing OSDP configuration in the Synergis™ Appliance Portal.
  7. Click Save.
    The channel and reader are created.
  8. From the hardware tree, select the OSDP channel you created and click Edit ().
  9. From the Bit rate list, select the bit rate you want to configure for your reader, and then select the Programming mode check box.
    If you have a configuration card, you can use it instead of Programming mode. See the documentation that came with your card.
    Dialog box for editing an OSDP channel in the Synergis™ Appliance Portal.
  10. Click Save.