Mercury reader address configuration for MR62e panel - Synergis Cloud Link 3.0.1

Synergis™ Cloud Link Administrator Guide 3.0.1

Product
Synergis™ Cloud Link
Content type
Guides > Administrator guides
Version
3.0
Release
3.0.1
ft:locale
en-US
Last updated
2024-01-22

Readers connected to the MR62e downstream panel are used in specific pairs and must be configured to predefined addresses, as hard-coded by Mercury, in order to work.

The following table shows the required reader address configuration:
Reader number (address) Door setup Mercury turnstiles and elevators
0 Door 1: Reader side IN Yes
1 Door 2: Reader side IN Yes
2 Door 1: Reader side OUT No
3 Door 2: Reader side OUT No
NOTE: To use the MR62e to control only one Card In/Card Out door, use addresses 0 and 2.

To use the MR62e to control two Card In/REX Out doors, use addresses 0 and 1.