Mercury reader address configuration for MR62e panel - Synergis™ Softwire 11.0

Synergis™ Softwire Integration Guide 11.0

series
Synergis™ Softwire 11.0
revised_modified
2020-11-27
category_custom
Guides
Guides > Integration guides
prodname_custom
Synergis > Synergis™ Softwire
vrm_version
11.0

Readers connected to the MR62e downstream panel must be addressed and used in specific pairs to work.

The following table shows the required reader address configuration:
Reader number (address) Door setup Mercury turnstiles and elevators
0 Door 1: Reader side IN Yes
1 Door 2: Reader side IN Yes
2 Door 1: Reader side OUT No
3 Door 2: Reader side OUT No
NOTE: To use the MR62e to control only one Card In/Card Out door, use addresses 0 and 2.

To use the MR62e to control two Card In/REX Out doors, use addresses 0 and 1.