You can configure the settings for your Mercury controllers in Synergis™ Appliance Portal.
Procedure
- Log on to the Synergis™ unit.
-
Click Configuration > Mercury controller settings.
-
Expand the PIN settings section, and configure the following
settings:
- Add leading zeros for PINs
- To define the number of zeros to be added before PINs, select
Custom, and enter a value for Leading
zeros. For example, the maximum PIN length is 4 digits long,
and you enter 3 as the Leading zeros value. If
your original PIN was 9, the PIN becomes 0009. If your
original PIN was 123, the PIN becomes
0123.
You must perform a software restart if you change this setting.
For more information, see Configuring PINs with leading zeros for Mercury integrations.
-
Expand the Door settings section, and enable the following
settings as required:
- Single held open mode
- Ignore subsequent Door open too long events after the first event is
generated, as long as the door remains
open.
You must perform a software restart if you change this setting.
- Raise card read events with the source event timestamp
- The timestamp from the Synergis™ Cloud
Link is used
instead of the timestamp from the Mercury
controller.
You must perform a software restart if you change this setting.
- Hide unlock events when 'Unlock on REX' is off
- The Mercury controller sends unlock events on REX activations regardless of
whether or not it actually unlocks the door. Enable this option to hide
these unlock events. Enabling this setting causes a delay on all events
received so that false unlock events can be filtered
out.
You must perform a software restart if you change this setting.
- Host decision handoff (offline mode)
- Mercury controllers make their own decisions as though they are disconnected from the Synergis™ Cloud Link. When the setting is enabled, some advanced features and cards that are not yet synchronized to the Mercury controller do not work, however, the door becomes much more responsive if there is lag or a bad network connection between the Synergis™ Cloud Link and Mercury controllers.
- Silent access granted
- Readers do not beep when access is granted.
- Silent access denied
- Readers do not beep when access is denied.
- Inhibit Door forced open event
- Door forced open events are
disabled.
You must perform a software restart if you change this setting.
- Reader LED off when locked
- Reader LEDs on OSDP readers are turned off if the associated door is in a normal lock state.
- Mercury native area control
- Enables Mercury's native antipassback, max occupancy, and interlock
features on the Mercury
panel.
You must perform a software restart if you change this setting.
- Extended grant time REX mode
- Doors remain unlocked for as long as the REX input is active and for the
normal grant time afterward. If no door sensor is present, the door remains
unlocked either for as long as the REX input is active or for the normal
grant time, whichever period is longer.
This is useful for preventing doors that are controlled by a motion sensor from locking and unlocking every few seconds. This feature requires Mercury firmware 1.29.1 or later.
You must perform a software restart if you change this setting.
NOTE: You can also configure this setting on a per door basis. - Program door alarm LED procedures
- Causes the readers associated with Mercury controllers to follow Synergis™
Softwire LED and buzzer patterns instead of
Mercury LED and buzzer patterns for door alarms.NOTE: If this option is disabled, when Door forced open and Door open too long events are generated, the LEDs on the associated readers do not flash.
You must perform a software restart and then reset the Mercury controllers if you change this setting.
-
Expand the Card conversions section, and enable the following
card conversions as required:
You must perform a software restart if you change any of these settings.
- Casi M5 56 -> 40
- Ambiguous HID 1441 -> 56
- Lossy conversion for credentials longer than 52 bits
- Fixes a bug in versions of Synergis™ Softwire earlier than 10.10, where credentials from 52 to 64 bits might have issues.
- 200 bits FASC-N to 128 bits
- All cards report the 128 bit version. This setting is used in conjunction with FICAM or Long credential database layouts.
- Add F2F to Wiegand translator
- Add or configure other translators.
-
Expand the Long credential formats section, and configure the
following setting:
- Wiegand format length (bits)
- Long credential formats for Mercury units are not automatically configured
in Security
Center. You must
manually set the format by entering a value from 64 to 240, and then
clicking Add. This setting is used in conjunction
with FICAM or Long credential database
layouts.
You must perform a software restart if you change this setting.
-
Expand the Advanced settings section, and enable the following
settings as required:
You must perform a software restart if you change any of these settings.
- SIO Encryption Control
- Enables encryption on the RS-485 between EP or Honeywell controllers and their downstream SIO boards, or LP controllers and older SIO boards. LP controllers with S3 SIO boards use encryption on the channel regardless of this setting.
- No ACR without door
- Readers are not pre-configured as SIO units are added, and I/O diagnostics do not report card reads from unassociated readers. This settings removes issues where more than 64 reader ports are enrolled under a Mercury controller or cases where readerless doors are being used that also go over the 64 limit.
-
Expand the Auxiliary authentication module section, and select
Disabled, PivClass, or
TIENtryPoint.
This setting is used in conjunction with FICAM database layout and the appropriate plugin for the LP4502 controller.
- Expand the Mercury SCP logging section, click Start logging for additional Mercury-specific logging, and enter the number of days after which you want the logging to end.
- Expand the Buses section, and click Reset for each controller or Reset all to ensure new settings are pushed to all the controllers.
-
Expand the Database layout settings section, and configure the
following settings:
-
Select a database layout from the list.
The Feature rich (default) layout fits most use cases. The other database layouts address specific needs. You must reset the controllers after changing the database layout.
For more information about what each database layout supports, see Database layouts for Mercury controllers.
-
Enter the Maximum PIN length.
The default value for all database layouts is 6. Lowering this value is commonly used to eliminate having to press the # key at the end of four-digit PINs when only four-digit PINs are used in the system.NOTE: Setting the Maximum PIN length to a number higher than what is supported by the selected database layout causes your Mercury controllers to stop functioning, and PINs longer than the configured Maximum PIN length do not work.You must perform a software restart if you change this setting.
-
Select a database layout from the list.
-
Expand the OSDP-reader-specific settings section, and
configure the following settings:
- Nexus and Veridt OSDP LED correction
- Fixes an LED issue that occurs in certain Nexus and Veridt OSDP readers.
-
Click Reset to default to reset all settings to default,
except for the database layout settings.
NOTE: There is no way to recover the previous settings.
- Click Save.