To have the Synergis™ unit communicate with the
Mercury controllers connected to it, you must enroll them using Security
Center
Config
Tool.
What you should know
Mercury controllers enrolled on a
Synergis™ unit are not visible from the Synergis™
Appliance Portal
Hardware page.On the Synergis™ unit, each Mercury controller must by assigned a
unique channel ID. All Mercury controllers have RS-485 buses to which the interface panels
(MR50, MR52, MR16IN, and MR16OUT) are connected. Each interface panel connected to the same
RS-485 or Ethernet bus must have a unique physical address.
Procedure
-
From the Config
Tool home page, open the
Access control task.
-
Click Roles and units, and then click the Synergis™ unit (
).
-
Click Peripherals, and then click Add an
item (
).
-
Enter the following information:
- Model
- Model of the controller.
- IP address
- Static IP address assigned to the controller by your IT department.
- Port
- Communication port (default=3001). The port must match the value configured on the
Mercury Device Manager web page.
- Channel
- Channel ID corresponding to this controller. The channel ID can be any value
between 0 and 63, and must be unique within the Synergis™ unit. Once assigned, it must not be
changed.
-
If the selected controller model supports downstream panels, add them.
NOTE: Consider the following:
-
Below the Interfaces group, click Add an
item (
).
-
In the dialog box that opens, select the Model, the
Port, the Address (0 to 31), and the
IP address (MR51e only) of the downstream panel.
All panels connected to the same port must use a different address.
-
Click OK.
-
Repeat as necessary.
-
(Optional) Click Advanced settings to change the advanced
settings.
The available settings depend on the selected controller model. You can typically
change the baud rate of the available serial port, the custom supervised input values, and
the power input event configuration.

NOTE: In Security
Center 5.8 or later and Synergis™
Softwire 10.8 or later, you can set up to four different
custom presets on your Mercury controller's inputs. For users upgrading from earlier
Security
Center versions who have a custom
value configured, that preset is listed as Custom 1 in the
AD limit rows list.
-
Click OK at the bottom of the dialog box.
-
Click Apply (
).
The Mercury controller with all its connected downstream panels and peripheral
devices are displayed on the
Peripherals page.

NOTE: Adding interface modules
to the Synergis™ unit causes the unit to perform
a software restart. During this process, the Synergis™ unit and all peripherals attached to it
appear offline (in red).
-
Select each of the discovered I/O devices and readers, and configure their properties as
necessary.
-
Test your wiring and configuration by triggering the inputs and outputs.
The triggered I/O changes state in real time on screen.
NOTE: Reader activities
are not shown in the Peripherals page.
After you finish
Add the MR51e panels to the
Mercury controller (if applicable), and then map the physical wiring of the interface
modules to the doors and zones in
Security
Center.