Interface modules come in all shapes and sizes and offer a wide range of features. Synergis™ Softwire supports most of the common features found on the market.
Synergis™
Softwire
11.1 supports the following HID VertX sub-panel features.
The following is the legend for some common values
found in the Supported column:
- Yes
- Feature is offered by the interface module and is supported by Synergis™ Softwire.
- No
- Feature is offered by the interface module but is not supported by Synergis™ Softwire.
- Not applicable
- Feature is not offered by the interface module.
Features | Supported |
---|---|
General characteristics | |
Category of interface module | Sub-panel |
Communication protocol | RS-485 |
Encrypted communication | Not applicable |
Online operation (connected to the Synergis™ unit) | |
Standalone mode | Not applicable |
Supervised mode | Not applicable |
Dependent mode | Yes |
Offline operation (no connection to the Synergis™ unit) | |
Standalone mode | Not applicable |
Degraded mode | Yes |
Reader communication protocols | |
Wiegand | Yes |
OSDP | Not applicable |
OSDP (Secure Channel) | Not applicable |
Clock and Data (Magnetic Stripe), also known as ABA format | Yes |
F2F | Not applicable |
Proprietary | Not applicable |
Scalability | |
Maximum number of offline events | Not applicable |
Maximum number of credentials (for autonomous decision making) | Not applicable |
Maximum credential length (in bits) | 1361 |
Maximum number of interface modules per Synergis™ unit RS-485 channel | 162 |
Recommended maximum number of interface modules per Synergis™ unit | 32 |
1 The certified limit is 136 bits. The actual limit might be higher.
2 Having many interface modules per channel decreases the polling rate per interface. This is a consideration if you have any PIN readers configured in mode 00, because you increase the chance of a digit being missed when someone enters their PIN quickly, resulting in a denied access.