Interface modules come in all shapes and sizes and offer a wide range of features. Synergis™ Softwire supports most of the common features found on the market.
- Yes
- Synergis Softwire supports the feature and the interface module offers it.
- No
- Synergis Softwire does not support the feature, but the interface module offers it.
- Not applicable
- The interface module does not offer the feature.
Features | Supported |
---|---|
General characteristics | |
Category of interface module | Intelligent controller |
Communication protocol | IP |
Encrypted communication | Yes |
Online operation (connected to the Synergis unit) | |
Standalone mode | Not applicable |
Supervised mode | No |
Dependent mode | Yes |
Offline operation (no connection to the Synergis unit) | |
Standalone mode | Yes |
Degraded mode | Not applicable |
Reader communication protocols | |
Wiegand | Yes |
OSDP | Yes |
OSDP (Secure Channel) | Yes5 |
Clock and Data (Magnetic Stripe), also known as ABA format | Not applicable |
F2F | Not applicable |
Proprietary | Not applicable |
Scalability | |
Maximum number of offline events | 30,0001 |
Maximum number of credentials (for autonomous decision making) | 15,0002 |
Maximum credential length (in bits) | 5123 |
Maximum number of interface modules per Synergis unit RS-485 channel | Not applicable |
Recommended maximum number of interface modules per Synergis unit | 30 or 664 |
1 There is not always a one-to-one match between an offline log entry and a Security Center event.
2 The recommended limit is 10,000. The hard limit is 15,000.
3 Supported card formats include Wiegand Standard 26-bit, Corporate 1000 (35-bit), H10306 (34-bit), H10302 (37-bit), and H10304 (37-bit). Custom card formats can go up to 512 bits.
4 The maximum for a Synergis™ Cloud Link is 30. The maximum for an SV-32, SV-100, or SV-300 is 66.
5 The minimum required versions are Synergis Softwire 11.3.0 and Axis 1601 firmware 1.84.4.