Not all Synergis™ appliance features are supported with the integration of Mercury controllers.
Synergis™ Appliance Portal and firmware features | Supported |
---|---|
Hardware configuration (pre-staging capability) | |
Manual enrollment (Add hardware dialog box) | No1 |
Automatic enrollment (Scan button) | No |
Property configuration | No |
Configuration cloning (Clone button) | No |
I/O diagnostics (live monitoring of inputs, relays, and readers) | No |
Interface module firmware display | No |
Interface module firmware upgrade | Manual |
Double-badge activation | Online2 |
Access control behavior (Synergis unit-wide settings) 3 | |
Interlock setting (Single door unlock or Single door open) | Not applicable |
Do not generate Door open too long events when door is unrestricted | Yes |
Reader setting (Card or PIN or Card only) | Yes4, 8 |
Maximum PIN length in digits 5 | 156, 7 |
1 Mercury controllers are enrolled using Config Tool.
2 Two swipes within 5 seconds by the same card unlocks the door until the same action locks it again.
3 The door behavior settings are overwritten by the individual door settings configured in Security Center.
4 A cardholder must have a card and one PIN credential for a PIN to work. A cardholder cannot have more than one PIN credential. Also, when set to Card or PIN, if a cardholder only has a PIN credential, that credential will not be synchronized to the controller and will not work. As a workaround, create and assign the cardholder a dummy card credential.
5 Mercury does not support keypad readers outputting PIN in 26-bit Wiegand mode (HID mode-14).
6 By default, maximum PIN length is set to six digits. For PINs under 6 digits, you must enter a '#' after the PIN.
7 By default, PINs that start with zero are not supported. For more information, see Configuring PINs with leading zeros for Mercury integrations.
8 The PIN value is not included in Access granted and Access denied events.