[KBA-79159] Readers connected to Mercury controllers are unresponsive
Cardholders cannot access doors controlled by readers connected to Mercury controllers.
Applies to
Synergis™ Softwire 11.4.0 - 11.4.2 | Synergis™ Cloud Link 2.1.0 and 3.0.0
Cause
Coding issue. Enrolling a Mercury LP or EP intelligent controller with more than 32 Mercury access control readers (ACRs) might cause the readers to become unresponsive on most or all doors when one of the following actions occurs:
- Adding a Mercury intelligent controller (LP or EP)
- Adding or deleting a Mercury downstream panel (MR board)
- Performing a System restart from the Softwire Synergis™ Appliance Portal
When performing one of the above actions, some of the configurations are not properly sent to the Mercury controller, causing some or all readers to lose their configuration, and thus, becoming unresponsive.
For more information on the calculation of the number of ACRs you have on a Mercury controller, see footnote 5 in Supported Mercury controller features in Synergis Softwire.
Workaround
Depending on the type of Synergis™ unit you have on your system, the workaround for this issue changes:
- Synergis™ Cloud Link (G2)
-
- Upgrade your unit to Synergis™ Cloud Link 3.0.0.
- Apply the hotfix HF3471139-01-3.0.0-3.0.259.0.sfw.
- Synergis™ Cloud Link (Legacy)
-
- Upgrade your unit to Synergis™ Softwire 11.4.2.
- Apply the hotfix HF3471139-02-11.4-11.4.1438.0.sfw.
- Streamvault™ appliance
-
- Upgrade your appliance to Synergis™ Softwire 11.4.2.
- Apply the hotfix HF3471139-03-11.4-11_4_1438_0.zip.
- Enable and disable the maintenance mode on doors
- Use this method when you have many affected doors.
- Open the Area view task.
- Select all affected doors, right-click your selection, and click .
- Wait for the synchronization to complete.
- Select again the same doors, right-click your selection, and click .
- Turn the reader shunting on and off
- Use this method when you have one affected reader on a door.
- Open the Access control task and click the Roles and units view.
- Select the affected Synergis unit and click the Peripherals tab.
- Select the affected reader and click Edit the item.
- In the Edit Reader dialog box, turn on the Shunted switch and click Save.
- Wait for the synchronization to complete.
- Select again the same reader and turn off the Shunted switch.
Status
This issue will be fixed in Synergis™ Softwire 11.5.0 and Synergis™ Cloud Link 3.1.0.