Mercury reader address configuration for MR62e panel - Synergis™ Softwire 10.11

Synergis™ Softwire Integration Guide 10.11

series
Synergis™ Softwire 10.11
revised_modified
2020-06-26

Readers connected to the MR62e downstream panel must be addressed and used in specific pairs to work.

The following table shows the required reader address configuration:
Reader number (address) Door setup Mercury turnstiles and elevators
0 Door 1: Reader side IN Yes
1 Door 2: Reader side IN Yes
2 Door 1: Reader side OUT No
3 Door 2: Reader side OUT No
NOTE: To use the MR62e to control only one Card In/Card Out door, use addresses 0 and 2.

To use the MR62e to control two Card In/REX Out doors, use addresses 0 and 1.