Adding two OSDP readers to one port on Mercury units - Synergis™ Softwire 10.11

Synergis™ Softwire Integration Guide 10.11

series
Synergis™ Softwire 10.11
revised_modified
2020-06-26

To use two OSDP readers on the same Mercury EP1501, LP1501, or MR51e controller, you must configure both readers to the first reader port of the controller.

What you should know

Mercury EP1501, LP1501, and MR51e controllers support up to two OSDP readers on port 1, which is terminal block TB2 for the EP1501 or LP1501, and TB3 for the MR51e. If you configure two OSDP readers on the first port, you cannot use the second port.

Mercury EP1501 and LP1501 must be enrolled without extension boards so the first reader port is available for the two OSDP readers.

Procedure

  1. In Config Tool, open the Access control task, and click Roles and units.
  2. From the entity tree, select the Synergis™ unit () and click Peripherals.
  3. Select Reader 1 (), click Edit (), and configure the following settings:
    • From the Type of Reader list, select OSDPv2.
    • From the Baud rate list, select the bit rate.
    • From the Address list, select the address you configured for the first reader.
  4. Repeat step 3 for Reader 2, using the address configured for the second reader.
    Selecting OSDPv2 for both readers automatically assigns both readers to the first port.
  5. (Optional, supported readers only) Ensure that the Secured option is set to ON.