[KBA-00901] Which HID VertX unit inputs can be used for general purposes?

On an HID VertX controller, AC Fail, Battery Fail, and REX inputs can be used for purposes other than what they are labeled for.

To use the AC Fail and Battery Fail inputs for other purposes, do the following:
  • In the Properties tab of the HID unit in Config Tool, ensure that the Monitor AC fail and Monitor battery ail options in the General settings section are cleared.
  • Ensure that the AC Fail and Battery Fail inputs on all the unit's interface modules (V100, V200, V300) are used for the same purpose, and are not used to monitor AC or battery failure.