Adding data points from Modbus devices to Security Center - Modbus 4.1

Modbus Plugin Guide 4.1

series
Modbus 4.1
revised_modified
2020-05-06

If a device template has not been created for the Modbus device you are adding to Security Center, you can manually add the data points of the device to Security Center.

What you should know

To add a data point to Security Center, you must enter its address. Addresses are provided by the device manufacturer.

Procedure

  1. From the Config Tool home page, open the Plugins task.
  2. Select a Modbus device from the entity browser, and then click the Properties tab.
  3. In the Data Point section, click the Add data point to Modbus device button ().
  4. In the Add data point dialog box, enter the following:
    Name
    The name of the data point.
    Modbus Object Type
    The object type of the data point. This can be a coil, discrete input, holding register, or input register.
    Address
    The address of the data point on the device.
    Type
    The data type that the data from the device will be transformed to.
    Unit
    The unit of measure of the data point. This field is optional.
    Unit symbol
    A symbol to represent the unit of measure of the data point. This field is optional.
  5. Click Save, and then click Apply.

Results

The data point is displayed in the Data Point section of the Properties tab.