To receive intrusion events and alarms from the Vanderbilt SPC Intrusion Panel in Security Desk, you must configure the intrusion detection unit in Config Tool.

Before you begin

Ensure that Config Tool and the Intrusion Manager role are on the same server.
WARNING: If you open Config tool from a server that does not host the Intrusion Manager, you will not see the correct Network card options for configuration in the Properties tab.

Procedure

  1. From the Config Tool homepage, open the Intrusion detection task.
  2. From the Intrusion Manager role in the entity browser, select the intrusion detection unit to configure.
  3. Click the Properties tab to configure the following properties.
    IP address
    The IP address of the selected intrusion detection unit.

    User information

    Username
    The name of the SPC panel user to connect the panel.
    PIN
    The PIN you configured on the panel for the selected user.

    Listener

    Network card
    The Genetecâ„¢ Server network card used to communicate with SPC intrusion panels.
    Port
    The Genetecâ„¢ Server TCP port used for SPC panel connections.
    NOTE: Refer to the FlexC and ATS configuration in the SPC Pro application.

    Outputs

    Keep output states synchronized
    Select this option to keep the output states from the intrusion detection unit synchronized with Security Center.
    Synchronization interval
    How often the output state of the intrusion detection unit gets synchronized with Security Center.

    Intrusion areas

    Synchronization interval
    How often the state of the intrusion detection area gets synchronized with Security Center.
    Default delayed arming time
    The default duration of the delay used by the delayed arming command. If a custom delay is set on the Security Desk widget, this default time is not used.
    Allow re-raising alarm events on an area already in alarm
    Select this option to allow Security Center to trigger another alarm on an area already in an Active alarm state. If this option is cleared, new alarms (for the same intrusion detection area) will only be triggered when the previous alarm has been acknowledged.
    Perimeter arming mapping
    Select the Partset mode to be used by the intrusion detection unit when a perimeter arming command is used by Security Center. Partset A or Partset B can be used in SPC panel configuration.

    Back up panel configuration

    Back up now
    Click to back up the panel configuration. Select the local folder to start the backup.
    Restore now
    Click to send a configuration file to the intrusion panel. Select the CFG file to start the restore.
    IMPORTANT: The Back up panel configuration section only appears if you are logged into the panel as an Engineer user, as configured in the User information section.
  4. Click Apply.