Access control hardware and sensors in the enclosure are connected to the terminals on the back of the Cloud Link Roadrunner™ unit.
Connection | Description |
---|---|
A | Connect a Cat5 network cable from the network switch to the LAN port. |
B | Up to two motorized locks can be connected to the LK1 and LK2 terminals. Locks can be installed in a new enclosure or can replace the locks in an existing enclosure. For more information, refer to the documentation included with the locks. |
C | Up to two door position sensors can be connected to the DPS1 and DPS2 terminals. |
D | Up to two card readers can be connected to the
RD1 and RD2
terminals. For more information, refer to the documentation
included with the readers. NOTE: The wire colors shown might not
reflect the hardware shipped. Refer the wiring information
included with the readers.
|
E | The unit supports four unsupervised inputs and two Form C relay outputs. |
F | Provide the unit with 22-26 Vdc (420mA mean / 724 mA peak). |
G | Ground the unit using the provided crimpable ground terminals and AWG 10-12 non-insulated wire. |