When an event occurs in SiPass, the plugin creates a custom event with the same name. In some cases, the plugin also creates a native Security Center event. Having a single SiPass event trigger both a custom event and a native event in Security Center ensures that automated actions for native events are generated as expected, while letting you specify different automated responses for the custom events.
For example, if SiPass communicates a Badge Collision event, you will see two events in the Monitoring task: Badge collision (a custom event) and Access Denied (a native event).
The following table shows the SiPass events that are mapped to native Security Center events and the related entities.
SiPass event | Security Center native event | Security Center entity |
---|---|---|
Access Denied | Access Denied | Area; Cardholder, Credential, Door, Elevator |
Access Granted | Access Granted | Area; Cardholder, Credential, Door, Elevator |
Access Not Granted | Access Denied | Area; Cardholder, Credential, Door, Elevator |
Access To AP Area | Access Granted | Area; Cardholder, Credential, Door, Elevator |
AC Power Failed | AC Fail | Access control unit, Intrusion detection unit |
APB Area Count Reset | People Count Reset | Area |
Bad Daily Code | Access Denied | Area; Cardholder, Credential, Door, Elevator |
Badge Collision | Access Denied | Area; Cardholder, Credential, Door, Elevator |
Battery Failed | Battery Fail | Access control unit, Intrusion detection unit |
Battery Low | Low battery | Access control unit |
Battery Low | Battery Fail | Access control unit, Intrusion detection unit |
Card At Disabled | Access Denied | Area; Cardholder, Credential, Door, Elevator |
Card Expired | Access Denied | Area; Cardholder, Credential, Door, Elevator |
Communication Lost | Unit Lost | Access control unit |
Communication Restored | Unit Connected | Access control unit, Intrusion detection unit |
Daily Code | Access Granted | Area; Cardholder, Credential, Door, Elevator |
Door Closed | Door Closed | Door |
Door Forced | Door Forced Open | Door |
Door Free | Door Unlocked: Maintenance Started | Door |
Door Held | Door Open Too Long | Door |
Door Locked | Door Locked | Door |
Door Secured | Door Locked: Maintenance Completed | Door |
Door TS Active | Scheduled Lock | Door |
Door Unlocked | Door Unlocked | Door |
Good Access | Access Granted | Area; Cardholder, Credential, Door, Elevator |
Group Error | Access Denied | Area; Cardholder, Credential, Door, Elevator |
Hard AP Error | Access Denied | Area; Cardholder, Credential, Door, Elevator |
Input Closed | Input Normal | Input |
Input Faulty | Input Trouble | Input |
Input Open | Input Active | Input |
Input Passback | Input Active | Input |
Input Tamper | Intrusion Detection Unit Tamper | Intrusion detection unit |
Input Tamper | Input Trouble | Input |
Intrusion Area Alarm | Intrusion Area Alarm Activated | Intrusion detection unit |
Intrusion Area Alarm | Intrusion Detection area alarm activated | Intrusion area |
Intrusion Area Armed | Intrusion Area Master Armed | Intrusion detection unit |
Intrusion Area Armed | Intrusion detection Area Master Arm | Intrusion area |
Intrusion Area Disarmed | Intrusion Area Disarmed | Intrusion detection unit |
Intrusion Area Disarmed | Intrusion Detection Area Disarmed | Intrusion area |
Intrusion Area Normal | Intrusion Detection Area Canceled Alarm | Intrusion area |
Intrusion Area Part Armed | Intrusion Detection Area Perimeter Arm | Intrusion area |
Intrusion Area PartB Armed | Intrusion Detection Area perimeter Arm | Intrusion area |
Invalid Facility | Access Denied | Area; Cardholder, Credential, Door, Elevator |
Invalid PIN | Access Denied | Area; Cardholder, Credential, Door, Elevator |
Low Battery | Battery Fail | Access control unit, Intrusion detection unit |
Not Yet Active | Access Denied | Area; Cardholder, Credential, Door, Elevator |
Point Alarm | Input Active | Input |
Point Normal | Input Normal | Input |
Point Tamper | Intrusion Detection Unit Tamper | Intrusion detection unit |
Power Lost | AC Fail | Access control unit, Intrusion detection unit |
Reader Timeout | Access Denied | Area; Cardholder, Credential, Door, Elevator |
Reentry Error | Access Denied | Area; Cardholder, Credential, Door, Elevator |
Soft AP Mode | Access Granted | Area; Cardholder, Credential, Door, Elevator |
Tamper Active | Input Trouble | Input |
TS Violation | Access Denied | Area; Cardholder, Credential, Door, Elevator |
Unit Comms Back | Unit Connected | Access control unit; Intrusion detection unit |
Unit Comms Lost | Unit Lost | Access control unit, Intrusion detection unit |
Unit Tamper Active | Hardware Tamper | Access control unit |
Unit Tamper Active | Hardware Tamper or Intrusion Detection Unit Tamper | Access control unit, Intrusion detection unit |
Void Card | Access Denied | Area; Cardholder, Credential, Door, Elevator |