When connecting hardware the Synergis™ Cloud Link appliance, use the recommended wire gauges.

Function Specification
RS-485 Belden 3105A or 9841 shielded cable or equivalent 22 AWG (maximum length of 4000 ft (1219 m) or 24 AWG (maximum length of 2500 ft (762 m)) shielded communications cable with a characteristic impedance of 120 ohm.
12 Volt (Synergis Cloud Link dc + input) 20 AWG (minimum)
Ground (Synergis Cloud Link dc - input) 20 AWG (minimum)