Synergis™ IX controllers support a wide range of access control features that depend on the version of Synergis™ Softwire you use.
Synergis™
Softwire
11.3 supports the following Synergis™ IX controller features.
The following is the legend for some common values
found in the Supported column:
- Yes
- Synergis™ Softwire supports the feature and the interface module offers it.
- No
- Synergis™ Softwire does not support the feature, but the interface module offers it.
- Not applicable
- The interface module does not offer the feature.
Features | Supported |
---|---|
General characteristics | |
Category of interface module (SY-SIX-CTRL-DIN or SY-SIX-CTRL-DIN-1D) | Intelligent controller |
Communication protocol | IP |
Encrypted communication | Yes (TLS 1.2) |
Online operation (connected to the Synergis™ unit) | |
Standalone mode | Yes |
Supervised mode | No |
Dependent mode | No |
Offline operation (no connection to the Synergis™ unit) | |
Standalone mode | Yes |
Degraded mode | Not applicable |
Reader communication protocols | |
Wiegand | Yes |
OSDP | Yes2 |
OSDP (Secure Channel) | Yes2 |
Clock and Data (Magnetic Stripe), also known as ABA format | No |
F2F | Not applicable |
Proprietary | Yes |
Scalability | |
Maximum number of credentials (for autonomous decision making) | 100,0001 for up to 4 controllers 25,0001 for up to 16 controllers |
Maximum credential length (in bits) | 643 |
Maximum number of interface modules per Synergis™ unit RS-485 channel | Not applicable |
Recommended maximum number of interface modules per Synergis™ unit | 16 |
1 Includes the two factory default users, which are read-only.
2 The only readers supported are HID Signo readers and Synergis™ IX OSDP readers. The minimum required versions for OSDP support are Synergis™ Softwire 11.2, Synergis™ IX controller firmware 4.00_649_L1C3, and reader expander firmware 1.12.585 L021.
3 Requires 11.3.2 or later. For more information, see About support for 64-bit credentials with Synergis™ IX.