Event types that can require acknowledgment conditions - Security Center 5.10

Security Center Administrator Guide 5.10

Applies to
Security Center 5.10
Last updated
2023-06-12
Content type
Guides > Administrator guides
Language
English
Product
Security Center
Version
5.10

Some event-to-actions can be configured so that a second event must be triggered before the alarm that was triggered can be acknowledged. The second event is the acknowledgment condition.

For example, you can configure a Signal lost event to trigger an alarm, and specify that the alarm can only be acknowledged after the Signal recovered event is generated.

The following table lists the event types that gives you the option to configure an acknowledgment condition that must be cleared before the alarm can be acknowledged.

Source event type Entity type Acknowledgment condition
AC fail Access control unit, Intrusion detection unit AC ready
Application lost Roles Application online
Asset offline Asset Asset online
Asset online Asset Asset offline
Battery fail Access control unit, Intrusion detection unit Battery ready
Deadbolt locked / unlocked Zone Input (Normal or Active)
Door closed Door, Zone Input (Normal or Active)
Door forced open Door, Zone Door closed

Input (Normal or Active)

Door locked / unlocked Door, Zone Input (Normal or Active)
Door manually unlocked Door, Zone Input (Normal or Active)
Door opened Door, Zone Door closed

Input (Normal or Active)

Door open too long Door Door closed
Door unsecured Door Door secured
Doorknob in place / rotated Zone Input (Normal or Active)
Entity warning Any entity that has an input Input (Normal or Active)
Glass break Zone Input (Normal or Active)
Hardware tamper Access control unit, Intrusion detection unit, Zone Tamper normal

Input (Normal or Active)

Intrusion detection area alarm activated Intrusion detection area Disarmed (not ready)

Disarmed (ready to arm)

Perimeter armed

Master armed

Intrusion detection area input bypass activated Intrusion detection area Input normal
Intrusion detection unit tamper Intrusion detection unit Tamper normal
Lock released / secured Zone Input (Normal or Active)
Manual station activated Door, Zone Manual station normal

Input (Normal or Active)

Manual station reverted to normal state Door, Zone Input (Normal or Active)
Motion off / on Zone1 Input (Normal or Active)
Record updated Record type, Zone Input (Normal or Active)
Recording problem Camera Recording problem resolved (corresponds to Recording on or Recording off)
Signal lost Camera Signal recovered
Unit lost Access control unit, Intrusion detection unit, ALPR unit, Video unit Unit online
Window closed / opened Zone Input (Normal or Active)
Zone armed / disarmed Zone Input (Normal or Active)
Zone maintenance completed / started Zone Input (Normal or Active)
Zone offline Zone Input (Normal or Active)

1 Only Motion on and Motion off events associated to zone input states can have an acknowledgment condition.